Commercial Tankless System
* Will have an empty slot in the manifold. These installations will require that the water/gas/condensate piping to be capped.
Up to 24 individual water heaters can be easily connected using multiples of CRK-BASE and CRK-ADDON kits. In order to ensure proper operation, a system controller (SC401-6M, SCU-401-12M or SCU-401-24M, sold separately) is required to en- sure system balancing and load management. Contact Noritz America for questions related to system controller selection or operation.
Manifold sizing is designed for a maximum of eight (8) water heaters. In order to connect units in greater number than eight, a common header of a larger diameter may be necessary. Refer to local plumbing and/or building code for minimum pipe sizing requirements.
Min. Common Gas Header | Min. Common Water Header | Min. Common Condensate Header | |
---|---|---|---|
Up to 8 units | 2 in | 2 in | 0.75 in |
>8 and <=16 | 2.5 in | 2.5 in | 1 in |
>16 and <=24 | 3 in | 3 in | 1.25 in |